A review of data center cooling technology, operating conditions and the corresponding low-grade waste heat recovery opportunities

Author keywords

Absorption refrigeration; Data center; Organic Rankine cycle; Thermoelectric; Waste energy reuse; Waste heat recovery

Indexed keywords

ABSORPTION COOLING; ABSORPTION REFRIGERATION; DESALINATION; ELECTRONIC COOLING; FOSSIL FUELS; GLOBAL WARMING; RANKINE CYCLE; RESERVOIRS (WATER); WASTE HEAT; WATER ABSORPTION;

EID: 84892912095     PISSN: 13640321     EISSN: None     Source Type: Journal    
DOI: 10.1016/j.rser.2013.12.007     Document Type: Review
Times cited : (540)

References (105)
  • 1
    • 84892935658 scopus 로고    scopus 로고
    • Pollution and the internet
    • Sept 23 Sect. A:1
    • Glanz J. Power, pollution and the internet. New York Times; Sept 23, 2012, Sect. A:1.
    • (2012) New York Times
    • Glanz, J.1
  • 2
    • 34247565733 scopus 로고    scopus 로고
    • Modeling of data center airflow and heat transfer: State of the art and future trends
    • DOI 10.1007/s10619-006-7007-3, High Density Data Centers
    • J. Rambo, and Y. Joshi Modeling of data center airflow and heat transfer: state of the art and future trends Distrib Parallel Database 21 2007 193 225 (Pubitemid 46673097)
    • (2007) Distributed and Parallel Databases , vol.21 , Issue.2-3 , pp. 193-225
    • Rambo, J.1    Joshi, Y.2
  • 3
    • 70350739203 scopus 로고    scopus 로고
    • Toward zero-emission data centers through direct reuse of thermal energy
    • (11)
    • T. Brunschwiler, B. Smith, E. Ruetsche, and B. Michel Toward zero-emission data centers through direct reuse of thermal energy IBM J Res Dev 53 3 2009 1 13 (11)
    • (2009) IBM J Res Dev , vol.53 , Issue.3 , pp. 1-13
    • Brunschwiler, T.1    Smith, B.2    Ruetsche, E.3    Michel, B.4
  • 4
    • 0041375424 scopus 로고    scopus 로고
    • Best practice guide for energy-efficient data center design. U.S. Department of Energy FEMP. NREL/BR-7A40-47201. DOE/GO-102010-2956
    • Best practice guide for energy-efficient data center design. U.S. Department of Energy FEMP. NREL/BR-7A40-47201. DOE/GO-102010-2956. Office of Energy Efficiency and Renewable Energy; 2011.
    • (2011) Office of Energy Efficiency and Renewable Energy
  • 5
    • 28144436675 scopus 로고    scopus 로고
    • A vision of energy aware computing from chips to data centers
    • Tsuchiura, Japan; Dec 1-3
    • Patel CD. A vision of energy aware computing from chips to data centers. In: Proceedings of ISMME 2003. Tsuchiura, Japan; Dec 1-3, 2003.
    • (2003) Proceedings of ISMME 2003
    • Patel, C.D.1
  • 7
    • 84867581723 scopus 로고    scopus 로고
    • Power-aware speed scaling in processor sharing systems: Optimality and robustness
    • A. Weirman, L.L.H. Andrew, and A. Tang Power-aware speed scaling in processor sharing systems: optimality and robustness Perform. Eval. 69 2012 601 622
    • (2012) Perform. Eval. , vol.69 , pp. 601-622
    • Weirman, A.1    Andrew, L.L.H.2    Tang, A.3
  • 8
    • 0003337211 scopus 로고    scopus 로고
    • Computational fluid dynamics modeling of high compute density data centers to assure system inlet air specifications
    • Kauai (HI, USA); 8-13 July
    • Patel CD, Bash CE, Belady C, Stahl L, Sullivan D. Computational fluid dynamics modeling of high compute density data centers to assure system inlet air specifications. In: Proceedings of IPACK'01. Kauai (HI, USA); 8-13 July, 2001.
    • (2001) Proceedings of IPACK'01
    • Patel, C.D.1    Bash, C.E.2    Belady, C.3    Stahl, L.4    Sullivan, D.5
  • 9
    • 4444266445 scopus 로고    scopus 로고
    • Data centers revisited: Assessment of the energy impact of retrofits and technology trends in a high-density computing facility
    • DOI 10.1061/(ASCE)1076-0342(2004), Sustainable Development and Infrastructure Systems
    • M. Blazek, H. Chong, W. Loh, and J.G. Koomey Data centers revisited: assessment of the energy impact of retroïts and technology trends in a high-density computing facility J Infrastruct Syst 10 2004 98 104 (Pubitemid 39174707)
    • (2004) Journal of Infrastructure Systems , vol.10 , Issue.3 , pp. 98-104
    • Blazek, M.1    Chong, H.2    Loh, W.3    Koomey, J.G.4
  • 10
    • 82055175102 scopus 로고    scopus 로고
    • Rate of heating analysis of data centers during power shutdown
    • K. Khankari Rate of heating analysis of data centers during power shutdown ASHRAE Trans 117 1 2011 212 221
    • (2011) ASHRAE Trans , vol.117 , Issue.1 , pp. 212-221
    • Khankari, K.1
  • 11
    • 70449469756 scopus 로고    scopus 로고
    • Data center evolution-A tutorial on state of the art, issues, and challenges
    • K. Kant Data center evolution-A tutorial on state of the art, issues, and challenges Comput Netw 53 2009 2939 2965
    • (2009) Comput Netw , vol.53 , pp. 2939-2965
    • Kant, K.1
  • 12
    • 84860433536 scopus 로고    scopus 로고
    • On-chip two-phase cooling of datacenters: Cooling systems and energy recovery evaluation
    • J.B. Marcinichen, J.A. Olivier, and J.R. Thome On-chip two-phase cooling of datacenters: cooling systems and energy recovery evaluation Appl Therm Eng 41 2012 36 51
    • (2012) Appl Therm Eng , vol.41 , pp. 36-51
    • Marcinichen, J.B.1    Olivier, J.A.2    Thome, J.R.3
  • 13
    • 79953246144 scopus 로고    scopus 로고
    • Coordinated optimization of cooling and IT power in data centers
    • 031006
    • E. Samadiani, H. Amur, B. Krishnan, Y. Joshi, and K. Schwan Coordinated optimization of cooling and IT power in data centers J Electron Packag 132 031006 2010 1 14
    • (2010) J Electron Packag , vol.132 , pp. 1-14
    • Samadiani, E.1    Amur, H.2    Krishnan, B.3    Joshi, Y.4    Schwan, K.5
  • 16
    • 58149216452 scopus 로고    scopus 로고
    • The thermal design of a next generation data center: A conceptual exposition
    • 041104
    • E. Samadiani, Y. Joshi, and F. Mistree The thermal design of a next generation data center: a conceptual exposition J Electron Packag 130 041104 2008 1 8
    • (2008) J Electron Packag , vol.130 , pp. 1-8
    • Samadiani, E.1    Joshi, Y.2    Mistree, F.3
  • 17
    • 75849141970 scopus 로고    scopus 로고
    • Designing environmentally sustainable electronic cooling systems using exergo-thermo-volumes
    • A.J. Shah, and C.D. Patel Designing environmentally sustainable electronic cooling systems using exergo-thermo-volumes Int J Energy Res 33 2009 1266 1277
    • (2009) Int J Energy Res , vol.33 , pp. 1266-1277
    • Shah, A.J.1    Patel, C.D.2
  • 18
    • 77957135558 scopus 로고    scopus 로고
    • Cooling of microprocessors with micro-evaporation: A novel two-phase cooling cycle
    • J.B. Marcinichen, J.R. Thome, and B. Michel Cooling of microprocessors with micro-evaporation: a novel two-phase cooling cycle Int J Refrig 33 7 2010 1264 1276
    • (2010) Int J Refrig , vol.33 , Issue.7 , pp. 1264-1276
    • Marcinichen, J.B.1    Thome, J.R.2    Michel, B.3
  • 19
    • 84861116312 scopus 로고    scopus 로고
    • Numerical prediction of the junction-to-fluid thermal resistance of a 2-phase immersion-cooled IBM dual core POWER6 Processor
    • San Jose (CA, USA); 18-22 March
    • Campbell L, Tuma P. Numerical prediction of the junction-to-fluid thermal resistance of a 2-phase immersion-cooled IBM dual core POWER6 Processor. In: Proceedings of the 28th IEEE SEMI-THERM symposium. San Jose (CA, USA); 18-22 March, 2012. p. 36-45.
    • (2012) Proceedings of the 28th IEEE SEMI-THERM Symposium , pp. 36-45
    • Campbell, L.1    Tuma, P.2
  • 21
    • 84860154455 scopus 로고    scopus 로고
    • Waste heat recovery in data centers using sorption systems
    • (021007)
    • A.B. Little, and S. Garimella Waste heat recovery in data centers using sorption systems J Therm Sci Eng Appl 4 2 2012 1 9 (021007)
    • (2012) J Therm Sci Eng Appl , vol.4 , Issue.2 , pp. 1-9
    • Little, A.B.1    Garimella, S.2
  • 25
    • 44649124233 scopus 로고    scopus 로고
    • Strategies for effective use of exergy-based modeling of data center thermal management systems
    • DOI 10.1016/j.mejo.2007.11.005, PII S002626920700362X
    • S. McAllister, V.P. Carey, A. Shah, C. Bash, and C. Patel Strategies for effective use of exergy-based modeling of data center thermal management systems Microelectron J 39 2008 1023 1029 (Pubitemid 351778426)
    • (2008) Microelectronics Journal , vol.39 , Issue.7 , pp. 1023-1029
    • McAllister, S.1    Carey, V.P.2    Shah, A.3    Bash, C.4    Patel, C.5
  • 26
    • 0003337211 scopus 로고    scopus 로고
    • Computational fluid dynamics modeling of high compute density data centers to assure system inlet air speciïcations
    • Kauai (HI, USA); July 8-13
    • Patel CD, Bash CE, Belady C, Stahl L, Sullivan D. Computational fluid dynamics modeling of high compute density data centers to assure system inlet air speciïcations. In: Proceedings of IPACK'01. Kauai (HI, USA); July 8-13, 2001.
    • (2001) Proceedings of IPACK'01
    • Patel, C.D.1    Bash, C.E.2    Belady, C.3    Stahl, L.4    Sullivan, D.5
  • 30
    • 1242309513 scopus 로고    scopus 로고
    • Multi-scale modeling of high power density data centers
    • Maui (HI, USA); July 6-11
    • Rambo J, Joshi Y. Multi-scale modeling of high power density data centers. In: Proceedings of IPACK'03. Maui (HI, USA); July 6-11,2003.
    • (2003) Proceedings of IPACK'03
    • Rambo, J.1    Joshi, Y.2
  • 31
    • 84993932836 scopus 로고    scopus 로고
    • Comparative analysis of different data center airflow management conïgurations
    • San Francisco (CA, USA); July 17-22
    • Shrivastav S, Sammakia B, Schmidt RR, Iyengar M. Comparative analysis of different data center airflow management conïgurations. In: Proceedings of IPACK'05. San Francisco (CA, USA); July 17-22, 2005.
    • (2005) Proceedings of IPACK'05
    • Shrivastav, S.1    Sammakia, B.2    Schmidt, R.R.3    Iyengar, M.4
  • 32
    • 84892923068 scopus 로고    scopus 로고
    • Optimization of data center room layout to minimize rack inlet air temperature
    • San Francisco (CA, USA); July 17-22
    • Bhopte S, Agonafer D, Schmidt RR, Sammakia B. Optimization of data center room layout to minimize rack inlet air temperature. In: Proceedings of IPACK'05. San Francisco (CA, USA); July 17-22, 2005.
    • (2005) Proceedings of IPACK'05
    • Bhopte, S.1    Agonafer, D.2    Schmidt, R.R.3    Sammakia, B.4
  • 33
    • 32844472688 scopus 로고    scopus 로고
    • Thermal characterization of non-raised floor air cooled data centers using numerical modeling
    • San Francisco (CA, USA); July 17-22
    • Iyengar M, Schmidt RR, Sharma A, McVicker G, Shrivastava S, Sri-Jayantha, S, et al. Thermal characterization of non-raised floor air cooled data centers using numerical modeling. In: Proceedings of IPACK'05. San Francisco (CA, USA); July 17-22, 2005.
    • (2005) Proceedings of IPACK'05
    • Iyengar, M.1    Schmidt, R.R.2    Sharma, A.3    McVicker, G.4    Shrivastava, S.5    Sri-Jayantha, S.6
  • 34
    • 14844363626 scopus 로고    scopus 로고
    • Balance of power: Dynamic thermal management for internet data centers
    • DOI 10.1109/MIC.2005.10
    • R.K. Sharma, C.E. Bash, C.D. Patel, R.J. Friedrich, and S.J. Chase Balance of power: dynamic thermal management for internet data centers IEEE Internet Comput 9 2005 42 49 (Pubitemid 40351898)
    • (2005) IEEE Internet Computing , vol.9 , Issue.1 , pp. 42-49
    • Sharma, R.K.1    Bash, C.E.2    Patel, C.D.3    Friedrich, R.J.4    Chase, J.S.5
  • 35
    • 84889617716 scopus 로고    scopus 로고
    • Thermal modeling of technology infrastructure facilities: A case study of data centers
    • W.J. Minkowycz, E.M. Sparrow, J.Y. Murthy, Taylor and Francis New York
    • J. Rambo, and Y. Joshi Thermal modeling of technology infrastructure facilities: a case study of data centers W.J. Minkowycz, E.M. Sparrow, J.Y. Murthy, The handbook of numerical heat transfer II 2006 Taylor and Francis New York 821 849
    • (2006) The Handbook of Numerical Heat Transfer , vol.II , pp. 821-849
    • Rambo, J.1    Joshi, Y.2
  • 36
    • 34247560899 scopus 로고    scopus 로고
    • Thermo-fluids provisioning of a high performance high density data center
    • DOI 10.1007/s10619-005-0413-0, High Density Data Centers
    • A.H. Beitelmal, and C.D. Patel Thermo-fluids provisioning of a high performance data center Distrib Parallel Database 21 2007 227 238 (Pubitemid 46673098)
    • (2007) Distributed and Parallel Databases , vol.21 , Issue.2-3 , pp. 227-238
    • Beitelmal, A.H.1    Patel, C.D.2
  • 37
    • 34247601764 scopus 로고    scopus 로고
    • Optimizing thermal design of data center cabinets with a new multi-objective genetic algorithm
    • DOI 10.1007/s10619-007-7009-9, High Density Data Centers
    • G. Li, M. Li, S. Azarm, J. Rambo, and Y. Joshi Optimization of data center cabinets with a new multi-objective genetic algorithm Distrib Parallel Database 21 2007 167 192 (Pubitemid 46673096)
    • (2007) Distributed and Parallel Databases , vol.21 , Issue.2-3 , pp. 167-192
    • Li, G.1    Li, M.2    Azarm, S.3    Rambo, J.4    Joshi, Y.5
  • 38
    • 79955692282 scopus 로고    scopus 로고
    • Energy efficient thermal management of data centers via open multi-scale design: A review of research questions and approaches
    • Y. Joshi, and E. Samadiani Energy efficient thermal management of data centers via open multi-scale design: a review of research questions and approaches J Enhanc Heat Transfer 18 1 2011 15 30
    • (2011) J Enhanc Heat Transfer , vol.18 , Issue.1 , pp. 15-30
    • Joshi, Y.1    Samadiani, E.2
  • 39
    • 84861150285 scopus 로고    scopus 로고
    • Datacenter power savings through high ambient datacenter operation: CFD modeling study
    • San Jose (CA, USA); March 18-22
    • Ahuja N. Datacenter power savings through high ambient datacenter operation: CFD modeling study. In: Proceedings of the 28th IEEE SEMI-THERM symposium. San Jose (CA, USA); March 18-22, 2012. p. 104-7.
    • (2012) Proceedings of the 28th IEEE SEMI-THERM Symposium , pp. 104-107
    • Ahuja, N.1
  • 40
    • 41649090202 scopus 로고    scopus 로고
    • Exergy analysis of data center thermal management system
    • 021401
    • A. Shah, V.P. Carey, C.E. Bash, and C.D. Patel Exergy analysis of data center thermal management system J Heat Transfer 130 021401 2008 1 10
    • (2008) J Heat Transfer , vol.130 , pp. 1-10
    • Shah, A.1    Carey, V.P.2    Bash, C.E.3    Patel, C.D.4
  • 41
    • 1242328132 scopus 로고    scopus 로고
    • High-end server low-temperature cooling
    • R.R. Schmidt, and B.D. Notohardjono High-end server low-temperature cooling IBM J Res Dev 46 6 2002 739 751
    • (2002) IBM J Res Dev , vol.46 , Issue.6 , pp. 739-751
    • Schmidt, R.R.1    Notohardjono, B.D.2
  • 42
    • 2342541636 scopus 로고    scopus 로고
    • Thermal management of harsh-environment electronics
    • San Jose (CA, USA); March 9-11
    • Ohadi M, Qi J Thermal management of harsh-environment electronics. In: Proceedings of the 20th IEEE SEMI-THERM symposium. San Jose (CA, USA); March 9-11, 2004.
    • (2004) Proceedings of the 20th IEEE SEMI-THERM Symposium
    • Ohadi, M.1    Qi, J.2
  • 44
    • 70449727078 scopus 로고    scopus 로고
    • PPT: Joint performance/power/thermal management of DRAM memory for multi-core systems
    • San Francisco (CA, USA); August 19-21
    • Lin CH, Yang CL, King KJ. PPT: joint performance/power/thermal management of DRAM memory for multi-core systems. In: Proceedings of the 14th ACM/IEEE ISLPED symposium. San Francisco (CA, USA); August 19-21, 2009. p. 93-8.
    • (2009) Proceedings of the 14th ACM/IEEE ISLPED Symposium , pp. 93-98
    • Lin, C.H.1    Yang, C.L.2    King, K.J.3
  • 46
    • 84892911577 scopus 로고    scopus 로고
    • 600 GByte, 3.5″, 15,000 rpm disk drive specification - 6 Gb SAS-2 interface. Sun Microsystems, Inc
    • - 600 GByte, 3.5″, 15,000 rpm disk drive specification - 6 Gb SAS-2 interface. Sun Microsystems, Inc. 〈http://docs.oracle.com/ cd/E19814-01/820-7290-10/820-7290-10.pdfâŒ.
  • 47
    • 84892948554 scopus 로고    scopus 로고
    • ®Green™Desktop hard drives. Western Digital Technologies, Inc.
    • ®Green™Desktop hard drives. Western Digital Technologies, Inc. 〈http://www.wdc.com/wdproducts/library/ SpecSheet/ENG/2879-701229.pdfâŒ.
  • 48
    • 0037392430 scopus 로고    scopus 로고
    • Efficient thermal management of data centers - Immediate and long-term research needs
    • C.E. Bash, C.D. Patel, and R.K. Sharma Efficient thermal management of data centers - immediate and long-term research needs HVAC&R Res 9 2 2003 137 152
    • (2003) HVAC&R Res , vol.9 , Issue.2 , pp. 137-152
    • Bash, C.E.1    Patel, C.D.2    Sharma, R.K.3
  • 50
    • 77958141523 scopus 로고    scopus 로고
    • Opportunities and challenges to unify workload, power and cooling management in data centers
    • Z. Wang, N. Tolia, and C. Bash Opportunities and challenges to unify workload, power and cooling management in data centers ACM SIGOPS Operating Syst Rev 44 3 2010 41 46
    • (2010) ACM SIGOPS Operating Syst Rev , vol.44 , Issue.3 , pp. 41-46
    • Wang, Z.1    Tolia, N.2    Bash, C.3
  • 52
    • 79951566319 scopus 로고    scopus 로고
    • Energy optimization of air-cooled data centers
    • 041005
    • H.E. Khalifa, and D.W. Demetriou Energy optimization of air-cooled data centers J Therm Sci Eng Appl 2 041005 2010 1 13
    • (2010) J Therm Sci Eng Appl , vol.2 , pp. 1-13
    • Khalifa, H.E.1    Demetriou, D.W.2
  • 55
    • 77953918683 scopus 로고    scopus 로고
    • Energy efficiency analyses and comparison of air and water cooled high-performance servers
    • San Francisco (CA, USA); July 19-23
    • Ellsworth MJ, Iyengar, MK. Energy efficiency analyses and comparison of air and water cooled high-performance servers. In: Proceedings of IPACK'09. San Francisco (CA, USA); July 19-23, 2009.
    • (2009) Proceedings of IPACK'09
    • Ellsworth, M.J.1    Iyengar, M.K.2
  • 57
    • 84861141325 scopus 로고    scopus 로고
    • Experimental characterization of an energy efficient chiller-less data center test facility with warm water cooled servers
    • San Jose (CA, USA); March 18-22
    • David MP, Iyengar M, Parida P, Simons R, Schultz M, Schmidt R, et al. Experimental characterization of an energy efficient chiller-less data center test facility with warm water cooled servers. In: Proceedings of the 28th IEEE SEMI-THERM symposium. San Jose (CA, USA); March 18-22, 2012. p. 232-7.
    • (2012) Proceedings of the 28th IEEE SEMI-THERM Symposium , pp. 232-237
    • David, M.P.1    Iyengar, M.2    Parida, P.3    Simons, R.4    Schultz, M.5    Schmidt, R.6
  • 58
    • 84861125184 scopus 로고    scopus 로고
    • Experimental investigation of water cooled server microprocessors and memory devices in an energy efficient chiller-less data center
    • San Jose (CA, USA); March 18-22
    • Parida PR, David M, Iyengar M, Schultz M, Gaynes, M, Kamath, V, et al. Experimental investigation of water cooled server microprocessors and memory devices in an energy efficient chiller-less data center. In: Proceedings of the 28th IEEE SEMI-THERM symposium. San Jose (CA, USA); March 18-22, 2012. p. 224-31.
    • (2012) Proceedings of the 28th IEEE SEMI-THERM Symposium , pp. 224-231
    • Parida, P.R.1    David, M.2    Iyengar, M.3    Schultz, M.4    Gaynes, M.5    Kamath, V.6
  • 60
    • 0035363424 scopus 로고    scopus 로고
    • Assessment of high-heat-flux thermal management schemes
    • DOI 10.1109/6144.926375, PII S1521333101047924
    • I. Mudawar Assessment of high-heat-flux thermal management schemes IEEE Trans Components Packag Manuf Technol 24 2001 122 141 (Pubitemid 32609745)
    • (2001) IEEE Transactions on Components and Packaging Technologies , vol.24 , Issue.2 , pp. 122-141
    • Mudawar, I.1
  • 61
    • 50949093804 scopus 로고    scopus 로고
    • Single-phase and two-phase hybrid cooling schemes for high-heat-flux thermal management of defense electronics
    • Orlando (FL, USA); May 28-31
    • Sung MK, Mudawar I. Single-phase and two-phase hybrid cooling schemes for high-heat-flux thermal management of defense electronics. In: Proceedings of ITHERM 2008, 11th intersociety conference. Orlando (FL, USA); May 28-31, 2008. p. 121-31.
    • (2008) Proceedings of ITHERM 2008, 11th Intersociety Conference , pp. 121-131
    • Sung, M.K.1    Mudawar, I.2
  • 63
    • 0028338022 scopus 로고
    • High flux boiling in low flow rate, low pressure drop mini-channel and micro-channel heat sinks
    • M.B. Bowers, and I. Mudawar High flux boiling in low flow rate, low pressure drop mini-channel and micro-channel heat sinks Int J Heat Mass Transfer 37 1994 321 332
    • (1994) Int J Heat Mass Transfer , vol.37 , pp. 321-332
    • Bowers, M.B.1    Mudawar, I.2
  • 64
    • 29144448697 scopus 로고    scopus 로고
    • The thermal bus opportunity-A quantum leap in data center cooling potential
    • DE-05-11-3, ASHRAE Transactions - Technical and Symposium Papers presented at the 2005 Annual Meeting of the American Society of Heating, Refrigerating and Air-Conditioning Engineers
    • P.L. Leonard, and A.L. Phillips The thermal bus opportunity-A quantum leap in data center cooling potential ASHRAE Trans 3 2 2005 732 745 (Pubitemid 41794858)
    • (2005) ASHRAE Transactions , Issue.111 PART 2 , pp. 732-745
    • Leonard, P.L.1    Phillips, A.L.2
  • 66
    • 83655204019 scopus 로고    scopus 로고
    • Flow boiling of R134a in a multi-microchannel heat sink hotspot heaters for energy-efficient microelectronic CPU cooling applications
    • Y. Madhour, J. Olivier, E. Costa-Patry, S. Paredes, B. Michel, and J.R. Thome Flow boiling of R134a in a multi-microchannel heat sink hotspot heaters for energy-efficient microelectronic CPU cooling applications IEEE Trans Components Packag Manuf Technol 1 6 2011 873 883
    • (2011) IEEE Trans Components Packag Manuf Technol , vol.1 , Issue.6 , pp. 873-883
    • Madhour, Y.1    Olivier, J.2    Costa-Patry, E.3    Paredes, S.4    Michel, B.5    Thome, J.R.6
  • 68
    • 44249094911 scopus 로고    scopus 로고
    • Recent advances in thermal modeling of micro evaporators for cooling of microprocessors
    • Seattle (WA, USA); November 11-15
    • Thome JR, Agostini B, Revellin R, Park JE. Recent advances in thermal modeling of micro evaporators for cooling of microprocessors. In: Proceedings of IMECE'07. Seattle (WA, USA); November 11-15, 2007.
    • (2007) Proceedings of IMECE'07
    • Thome, J.R.1    Agostini, B.2    Revellin, R.3    Park, J.E.4
  • 69
    • 84892911271 scopus 로고    scopus 로고
    • Refrigerated cooling of microprocessors with micro-evaporation heat sinks: New developments and energy prospects for green data centers
    • 2008/9
    • Thome JR, Bruch A. Refrigerated cooling of microprocessors with micro-evaporation heat sinks: new developments and energy prospects for green data centers. IOR Proceedings, vol. 105; 2008/9.
    • IOR Proceedings , vol.105
    • Thome, J.R.1    Bruch, A.2
  • 70
    • 77956225708 scopus 로고    scopus 로고
    • The steady-state modeling and optimization of a refrigeration system for high heat flux removal
    • R. Zhou, T. Zhang, J. Catano, J.T. Wen, C.J. Michna, and Y. Peles et al. The steady-state modeling and optimization of a refrigeration system for high heat flux removal Appl Therm Eng 30 2010 2347 2356
    • (2010) Appl Therm Eng , vol.30 , pp. 2347-2356
    • Zhou, R.1    Zhang, T.2    Catano, J.3    Wen, J.T.4    Michna, C.J.5    Peles, Y.6
  • 71
    • 71849092314 scopus 로고    scopus 로고
    • Saturated critical heat flux in a multi-microchannel heat sink fed by a split flow system
    • A.W. Mauro, J.R. Thome, D. Toto, and G.P. Vanoli Saturated critical heat flux in a multi-microchannel heat sink fed by a split flow system Exp Therm Fluid Sci 34 1 2010 81 92
    • (2010) Exp Therm Fluid Sci , vol.34 , Issue.1 , pp. 81-92
    • Mauro, A.W.1    Thome, J.R.2    Toto, D.3    Vanoli, G.P.4
  • 74
    • 84892947993 scopus 로고    scopus 로고
    • Viewed October 7, 2012
    • 〈http://www.eia.gov/consumption/residential/ âŒ, Viewed October 7, 2012.
  • 75
    • 84928016608 scopus 로고    scopus 로고
    • The Guardian 2010 July 20
    • Vela, J. Helsinki data centre to heat homes. The Guardian 2010 July 20. 〈http://www.guardian.co.uk/environment/2010/jul/20/ helsinki-data-centre-heat-homesâŒ.
    • Helsinki Data Centre to Heat Homes
    • Vela, J.1
  • 76
    • 84892926128 scopus 로고    scopus 로고
    • District heating and cooling enable efficient energy resource utilisation
    • A. Gebremedhin, InTech Rijeka (published online)
    • D. Henning, and A. Gebremedhin District heating and cooling enable efficient energy resource utilisation A. Gebremedhin, Sustainable energy - recent studies 2012 InTech Rijeka (published online)
    • (2012) Sustainable Energy - Recent Studies
    • Henning, D.1    Gebremedhin, A.2
  • 77
    • 84859420465 scopus 로고    scopus 로고
    • District heating in sequential energy supply
    • U. Persson, and S. Werner District heating in sequential energy supply Appl Energy 95 2012 123 131
    • (2012) Appl Energy , vol.95 , pp. 123-131
    • Persson, U.1    Werner, S.2
  • 78
    • 84892943642 scopus 로고    scopus 로고
    • Data center heat recovery helps Intel create green facility
    • Data center heat recovery helps Intel create green facility. Intel 2007. 〈http://www.intel.com/content/www/us/en/green-it/ energy-efficiency/intel-it-data-center-heat-recovery-helps-create-green- facility-brief.htmlâŒ.
    • Intel 2007
  • 82
    • 84862819572 scopus 로고    scopus 로고
    • A review of working fluids of absorption cycles
    • J. Sun, L. Fu, and S. Zhang A review of working fluids of absorption cycles Renew Sustain Energy Rev 16 4 2012 1899 1906
    • (2012) Renew Sustain Energy Rev , vol.16 , Issue.4 , pp. 1899-1906
    • Sun, J.1    Fu, L.2    Zhang, S.3
  • 84
    • 84862819873 scopus 로고    scopus 로고
    • Thermodynamic feasibility of harvesting data center waste heat to drive an absorption chiller
    • A. Haywood, J. Sherbeck, P. Phelan, G. Varsamopoulos, and S.K.S. Gupta Thermodynamic feasibility of harvesting data center waste heat to drive an absorption chiller Energy Convers Manage 58 2012 26 34
    • (2012) Energy Convers Manage , vol.58 , pp. 26-34
    • Haywood, A.1    Sherbeck, J.2    Phelan, P.3    Varsamopoulos, G.4    Gupta, S.K.S.5
  • 86
    • 84864369608 scopus 로고    scopus 로고
    • Thermodynamic analysis of an absorption refrigeration system with ionic-liquid/refrigerant mixture as a working fluid
    • Y.J. Kim, S. Kim, Y.K. Joshi, A.G. Fedorov, and P.A. Kohl Thermodynamic analysis of an absorption refrigeration system with ionic-liquid/refrigerant mixture as a working fluid Energy 44 2012 1005 1016
    • (2012) Energy , vol.44 , pp. 1005-1016
    • Kim, Y.J.1    Kim, S.2    Joshi, Y.K.3    Fedorov, A.G.4    Kohl, P.A.5
  • 87
    • 36749052356 scopus 로고    scopus 로고
    • An absorption based miniature heat pump system for electronics cooling
    • DOI 10.1016/j.ijrefrig.2007.07.003, PII S0140700707001302
    • Y.J. Kim, Y.K. Joshi, and A.G. Fedorov An absorption based miniature heat pump system for electronics cooling Int J Refrig 31 1 2008 23 33 (Pubitemid 350216907)
    • (2008) International Journal of Refrigeration , vol.31 , Issue.1 , pp. 23-33
    • Kim, Y.J.1    Joshi, Y.K.2    Fedorov, A.G.3
  • 88
    • 84864369209 scopus 로고    scopus 로고
    • Absorption heat pump/refrigeration system utilizing ionic liquid & hydrofluorocarbon refrigerants
    • 031009
    • S. Kim, Y.J. Kim, Y.K. Joshi, A.G. Fedorov, and P.A. Kohl Absorption heat pump/refrigeration system utilizing ionic liquid & hydrofluorocarbon refrigerants J Electron Packag 134 031009 2012 1 9
    • (2012) J Electron Packag , vol.134 , pp. 1-9
    • Kim, S.1    Kim, Y.J.2    Joshi, Y.K.3    Fedorov, A.G.4    Kohl, P.A.5
  • 89
    • 40449102974 scopus 로고    scopus 로고
    • Miniaturized refrigeration system with absorption application to microelectronics cooling
    • Vancouver (Canada), 8-12 July 2007
    • Chiriac V, Chiriac F. Miniaturized refrigeration system with absorption application to microelectronics cooling. In: Proceedings of ASME InterPACK'07. Vancouver (Canada), 8-12 July 2007.
    • Proceedings of ASME InterPACK'07
    • Chiriac, V.1    Chiriac, F.2
  • 90
    • 77955223523 scopus 로고    scopus 로고
    • Absorption refrigeration method with alternative water-ammonia solution circulation system for microelectronics cooling
    • Las Vegas (NV, USA); June 2-5
    • Chiriac V, Chiriac F. Absorption refrigeration method with alternative water-ammonia solution circulation system for microelectronics cooling. In: Proceedings of ITHERM 2010, 12th intersociety conference. Las Vegas (NV, USA); June 2-5, 2010.
    • (2010) Proceedings of ITHERM 2010, 12th Intersociety Conference
    • Chiriac, V.1    Chiriac, F.2
  • 91
    • 77957067873 scopus 로고    scopus 로고
    • A review of thermodynamic cycles and working fluids for the conversion of low-grade heat
    • H. Chen, D.Y. Goswami, and E.K. Stefanakos A review of thermodynamic cycles and working fluids for the conversion of low-grade heat Renew Sustain Energy Rev 14 2010 3059 3067
    • (2010) Renew Sustain Energy Rev , vol.14 , pp. 3059-3067
    • Chen, H.1    Goswami, D.Y.2    Stefanakos, E.K.3
  • 92
    • 0031011385 scopus 로고    scopus 로고
    • A review of organic rankine cycles (ORCs) for the recovery of low-grade waste heat
    • DOI 10.1016/S0360-5442(96)00165-X, PII S036054429600165X
    • T.C. Hung, T.Y. Shai, and S.K. Wang A review of organic Rankine cycles (ORCs) for the recovery of low-grade waste heat Energy 22 7 1997 661 667 (Pubitemid 27206837)
    • (1997) Energy , vol.22 , Issue.7 , pp. 661-667
    • Hung, T.C.1    Shai, T.Y.2    Wang, S.K.3
  • 93
    • 84876537293 scopus 로고    scopus 로고
    • A review of working fluid and expander selections for organic Rankine cycle
    • J. Bao, and L. Zhao A review of working fluid and expander selections for organic Rankine cycle Renew Sustain Energy Rev 24 2013 325 342
    • (2013) Renew Sustain Energy Rev , vol.24 , pp. 325-342
    • Bao, J.1    Zhao, L.2
  • 94
    • 84860224290 scopus 로고    scopus 로고
    • A technical, economical and market review of organic Rankine cycles for the conversion of low-grade heat for power generation
    • F. Vélez, J.J. Segovia, M.C. Martín, G. Antolín, F. Chejne, and A. Quijano A technical, economical and market review of organic Rankine cycles for the conversion of low-grade heat for power generation Renew Sustain Energy Rev 16 6 2012 4175 4189
    • (2012) Renew Sustain Energy Rev , vol.16 , Issue.6 , pp. 4175-4189
    • Vélez, F.1    Segovia, J.J.2    Martín, M.C.3    Antolín, G.4    Chejne, F.5    Quijano, A.6
  • 95
    • 80051796336 scopus 로고    scopus 로고
    • Low-grade heat conversion into power using organic Rankine cycles - A review of various applications
    • B.F. Tchanche, Lambrinos Gr, A. Frangoudakis, and G. Papadakis Low-grade heat conversion into power using organic Rankine cycles - a review of various applications Renew Sustain Energy Rev 15 2011 3963 3979
    • (2011) Renew Sustain Energy Rev , vol.15 , pp. 3963-3979
    • Tchanche, B.F.1    Gr, L.2    Frangoudakis, A.3    Papadakis, G.4
  • 96
    • 33947386631 scopus 로고    scopus 로고
    • Working fluids for low-temperature organic Rankine cycles
    • DOI 10.1016/j.energy.2006.07.001, PII S0360544206001812
    • B. Saleh, G. Koglbauer, M. Wendland, and J. Fischer Working fluids for low-temperature organic Rankine cycles Energy 32 2007 1210 1221 (Pubitemid 46453001)
    • (2007) Energy , vol.32 , Issue.7 , pp. 1210-1221
    • Saleh, B.1    Koglbauer, G.2    Wendland, M.3    Fischer, J.4
  • 98
    • 84866175792 scopus 로고    scopus 로고
    • Design of a microscale organic Rankine cycle for high-concentration photovoltaics waste thermal power generation
    • San Diego (CA, USA); May 30-June 1
    • Zhang T, Wang EN. Design of a microscale organic Rankine cycle for high-concentration photovoltaics waste thermal power generation. In: Proceedings of ITHERM 2012, 13th intersociety conference. San Diego (CA, USA); May 30-June 1, 2012. p. 993-1002.
    • (2012) Proceedings of ITHERM 2012, 13th Intersociety Conference , pp. 993-1002
    • Zhang, T.1    Wang, E.N.2
  • 99
    • 84876475145 scopus 로고    scopus 로고
    • Nanoengineering thermoelectrics for 21st century: Energy harvesting and other trends in the field
    • M. Martín-González, O. Caballero-Calero, and P. Díaz-Chao Nanoengineering thermoelectrics for 21st century: energy harvesting and other trends in the field Renew Sustain Energy Rev 24 2013 288 305
    • (2013) Renew Sustain Energy Rev , vol.24 , pp. 288-305
    • Martín-González, M.1    Caballero-Calero, O.2    Díaz-Chao, P.3
  • 100
    • 0035846181 scopus 로고    scopus 로고
    • Thin-film thermoelectric devices with high room-temperature figures of merit
    • DOI 10.1038/35098012
    • R. Venkatasubramanian, E. Siivola, T. Collpitts, and B. O'Qinn Thin-film thermoelectric devices with high-room temperature figure of merit Nature 413 2001 597 602 (Pubitemid 32964053)
    • (2001) Nature , vol.413 , Issue.6856 , pp. 597-602
    • Venkatasubramanian, R.1    Siivola, E.2    Colpitts, T.3    O'Quinn, B.4
  • 103
    • 80054851973 scopus 로고    scopus 로고
    • Techno-economic feasibility of absorption heat pumps using wastewater as the heating source for desalination
    • H. Li, N. Russell, V. Sharifi, and J. Swithenbank Techno-economic feasibility of absorption heat pumps using wastewater as the heating source for desalination Desalination 281 2011 118 127
    • (2011) Desalination , vol.281 , pp. 118-127
    • Li, H.1    Russell, N.2    Sharifi, V.3    Swithenbank, J.4


* 이 정보는 Elsevier사의 SCOPUS DB에서 KISTI가 분석하여 추출한 것입니다.